Agreed. 48V (actually -48V) has been used across telco central offices for decades.
by mccoyc 3y ago
Agreed. 48V (actually -48V) has been used across telco central offices for decades.
- kurthr 3y agoIt's a really nice voltage with lots of support for batteries and up/dn conversion hardware. It's also right at the edge of what is human safe. You can burn yourself and blow up cables, but it's very difficult to electrocute yourself (afib or muscle seize) without lots of wet contact. https://incompliancemag.com/article/experiments-of-dc-human-body-resistance-i/ https://incompliancemag.com/article/experiments-of-dc-human-...
- jacquesm 3y agoIndeed, I'm aware of only one recorded death by electrocution at 48V, iirc it was a Swiss radio amateur that had done a bunch of gardening sat down sweaty in a metallic chair and reached for the one switch of his set. Probably there were other contributory causes as well, I've been zapped multiple times from much higher voltage sources (that could have easily supplied the power required) and lived. I can't find a reference for that Swiss case though. I'll keep looking.
- IgorPartola 3y agoI assume if you didn’t live from those zaps you wouldn’t be here making this comment.
- jacquesm 3y agoHaha, fair point, yes, indeed. The most clear form of survivorship bias, thank you for pointing it out.
- firebat45 3y agoHow exactly do you define a negative voltage unless you are using some other voltage as a reference?
- dragontamer 3y agoLabel the power pin+ GND and the power pin- becomes -48V Voltages are all relative. It's like saying 'How do you get a height difference of 10 feet by digging?' Well, you dig and then label the initial level as +10 feet, and redefine the bottom of your hole to be ground.
- Kirby64 3y agoNo. In telco, the -48V is referenced against ground, like the physical ground. If you're isolated, you can do this. but they would still need to be referencing the 'ground' to something ... likely the negative side of the main battery pack. The reason why -48V is used is because it is provided as a bias voltage to give wiring cathodic protection, to prevent corrosion of telecom infrastructure. If you used 48V, it would not work. You need a negative voltage referenced against ground.
- applied_heat 3y agoGround positive terminal of battery string instead of grounding negative terminal. I see this more often on European stuff
- bluGill 3y agoGenerally with respect to ground. There are many good reasons to connect your power system to ground and so this is commonly done. (there are pros and cons to connecting to ground, but it gets complex fast)
- myself248 3y agoIt is with respect to ground, the positive pole of the battery is connected to ground. The telegraph system figured this out very quickly. Most water in nature has at least a bit of salt in it, which is present as positive sodium ions and negative chloride ions. By making the outdoor wiring negative with respect to ground, the chloride ions are repelled, and such wires corrode much more slowly than those that're positive with respect to ground. Since most of the telegraph network, later the telephone network, is outdoors, this is a pretty big deal.